TM 5-3810-307-24-1-2
10. DRAWING 18. CONNECTION BOARD IN CENTRAL UNIT
THE VOLTMETER SHOULD MEASURE THE FOLLOWING BETWEEN TERMINALS X1:8
(GROUND) AND X:10 (LENGTH SIGNAL):
0.5 VOLTS WITH THE BOOM FULLY RETRACTED AND LENGTH
POTENTIOMETER SET FULLY COUNTERCLOCKWISE TO A SOFT STOP
(MINIMUM SENSOR OUTPUT)
2.1 VOLTS ( 0.1 V) WITH THE BOOM FULLY EXTENDED (ACTUAL WORKING
RANGE)
4.5 VOLTS WITH THE LENGTH POTENTIOMETER TURNED COMPLETELY
CLOCKWISE 10 TURNS TO A SOFT STOP (MAXIMUM SENSOR OUTPUT)
REFER TO DRAWING 2 FOR WIRING DIAGRAM.
REFER TO DRAWING 3 FOR BOARD LOCATION.